Piping DiagramSamsung Electronics 221Main heating operationƒ PurposeSwitch to cooling mode on some indoor units while using heating mode.ƒ Control specifications in detail7-3 Functions (cont.)7-3-2-3 Normal operation modes (cont.)7-3-2 Control (cont.)Actuator Abbrev. - Normal CoolingCompressor COMP Operation Target high pressure control(default : 28kgf/ )Range 14 - 120HzElectronic Expansion Valve– Main (Main EEV) E_M Operation Target SH controlRange 125step ~ 2000stepElectronic Expansion Valve– EVI (EVI EEV) E_EVI Operation Vapor injection controlRange 0-480stepSolenoid Valve - 4way V_4W Operation OnSolenoid Valve – EVI Bypass V_EB Operation On (Open): *T_w > 28ఁ or 50Hz ײOff (Close): T_w < 25ײఁ and 65Hz װSolenoid Valve – EVI V_EVI Operation On (Open)Solenoid Valve – Hot Gas Bypass V_HG Operation Off (Close)Solenoid Valve – Accumulator Oil Return V_AR Operation On (Open)Solenoid Valve – Hot Gas Bypass 2 V_HG2 Operation Off(Close)Solenoid Valve-Liquid Tube V_L Operation Off (Close)Solenoid Valve – Main Cooling V_MC Operation Off (Close)Solenoid Valve-Hot Gas Charging V_HC Operation Off(Close)