E-9ENGLISHFixing the Installation PlatePurging the Indoor UnitThe indoor unit is supplied with inert gas (nitrogen).Before installing the unit, check if nitrogen gas flow out of indoor unit.If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be insidethe indoor unit.Unscrew the caps at the end of each pipe.Result: All inert gas exhausts from the indoor unit. To prevent dirt or foreign substances from getting into the pipes duringinstallation, do NOT remove the caps completely until you are ready toconnect the pipes.INSTALLING THE A IR CONDTIONERBefore fixing the installation plate to the wall or window frame, you mustdetermine the position of the 65mm hole through which the cable, pipe andhose pass to connect the indoor unit to the outdoor unit.When facing the wall, the pipe and cable can be connected from the: Right Left Underside (right) Rear (right or left)1 Determine the position of the pipe and drain hose hole as seen in the pictureand drill the hole with an inner diameter of 65mm so that it slants slightlydownwards.2 If you fix the indoor unit to a... Follow step(s)...Wall 3.Window frame 4 to 6.3 Fix the installation plate to the wall giving attention to the weight of theindoor unit. If you mount the plate to a concrete wall with anchor bolts, the anchorbolts must not project more than 20mm.4 Determine the positions of the wooden uprights to be attached to thewindow frame.5 Attach the wooden uprights to the window frame giving attention to theweight of the indoor unit.6 Attach the installation plate to the wooden uprights using tapping screws asseen in the picture.120726872(Unit : mm)Pipe hole(Ø65mm)140346834(Unit : mm)Pipe hole(Ø65mm)18/2409/1208'FORTE_VIVACE_Inv_IM_28492A£¨4£©_E.indd 9 2007-12-6 9:32:38