E-42Tracking (Continued)7 Message will appear to alert that tracking is completed. Select the zone initializingmode and click [OK]. No initialization: No zone information initialization will be made. Individual initialization: Initialize zone information as individual mode. Group initialization: Initialize zone information as group mode.8 Page will be refreshed by clicking [OK]. Then you can check the tracking result.Note If tracking is executed successfully with interface module set for communication modesetting for each channel, virtual centralized controller will be assigned to each channel. For the address of the virtual centralized controller, Channel 0 will be set to 11,Channel 1 to 12, Channel 2 to 13, channel 3 to 14 and channel 4 to 15. If there is existing communication channel for interface module, tracking for centralizedcontroller will be limited to range of 0 ~ 10. If you cannot find any devices after tracking, it will be considered as a DVM trackingfailure If there are devices which have same address, only first searched device will beregistered. The number of centralized controller contains the number of virtual centralizedcontrollerwhich is used in interface module communication. The number of indoor unit contains the number of indoor unit, ERV and AHU kit. If you execute tracking, system setting will be initialized. If tracking result does not match with actual installation information, there can becritical error in additional functions such as power distribution. Make sure that tracking information matches to actual installation informationafter tracking.7