E-60 You may use ALL_OFF command to turn on all the indoor units but it is notrecommended. If communication error occurs on devices such as SIM/Centralized Controller/Interface Module etc, other functions such as power distribution may alsocreate a problem. You must have BMS system to check the errors and you musttake action immediately.BACnet Point List (Continued)Single Centralized controller has following point list.InstanceNumber Object ObjectType Object Name Status value1 Centralized controller errorcode AI Central_Error_CodeRefer to the list of theintegrated error codeCentralized controllerInstanceNumber Object ObjectType Object Name Status value1 Interface module error code AI Repeater_Error_CodeRefer to the list of theintegrated error codeSingle Interface module has following point list.Interface moduleInstance Control and Monitoring ObjectType Object Name Status Value1 All device OFF BO ALL_OFF Inactive : All devices Off2 DMS2 Status AI DMS2_Status0: Normal, 8: Emergencystop, 105 : Tracking inprogress, 108 : Trackingfailed3 BACnet error code AI BACnetApp_Error_Code BACnet error codeBACnet Gateway has following point list.BACnet Gateway