Indoor Unit14. Installation54Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXXOption SEG1 SEG2 SEG3 SEG4Explanation PAGE MODERESERVEDUse of externaltemperature sensorIndicationand DetailsIndication Details Indication Details Indication Details0 2 0 Disuse1 UseOption SEG5 SEG6 SEG7 SEG8Explanation Use of central controlRESERVEDPAGE Use of drain pumpIndicationand DetailsIndication Details Indication Details Indication Details0 Disuse10 Disuse1 Use1 Use2 Use + 3minutedelayOption SEG9 SEG10 SEG11 SEG12Explanation Use of Hot Coil Use of heater Controller variables for auxiliaryheaterRESERVEDIndicationand DetailsIndication Details Indication DetailsIndicationDetails0 Disuse 0 DisuseSettemperaturefor auxiliaryheat onTime delayfor auxiliaryheat on0 Notemperatureoffset No delay1 Notemperatureoffset 10 minutes2 Notemperatureoffset 20 minutes1 Use 1 Use3 1.5°C No delay4 1.5°C 10 minutes5 1.5°C 20 minutes6 3°C No delay7 3°C 10 minutes8 3°C 20 minutes- - 2 Use(Heater time delay)9 4.5°C No delayA 4.5°C 10 minutesB 4.5°C 20 minutesC 6°C No delayD 6°C 10 minutesE 6°C 20 minutesOption SEG13 SEG14 SEG15 SEG16Explanation PAGE Use of external control Setting the output of externalcontrol S-Plasma ionIndicationand DetailsIndication Details Indication Details Indication Details Indication Details20 DisuseSlave(disableLevelcontrol*)0 Thermo on 0 Disuse1 On/Off control2 Off control3 Window on/off control4 Disuse Master(enableLevelcontrol*)1 Operation on 1 Use5 On/Off control6 Off control7 Window on/off control