D440-03-00 1 I56-3475-000RTS151KEYARemote Test StationINSTALLATION AND MAINTENANCE INSTRUCTIONS6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T51-800-SENSOR2, FAX: 905-812-0771www.systemsensor.caNOTE: RTS151KEYA replaces RTS451KEYA.NOTICE: This manual shall be left with the owner/user of this equipment.NOTE: A test coil is required only for use with D2A,DNRA,DH400A,DH500Amodels. For D2A models order part # DCOIL. For DH400A/500A modelsorder part #Coil.GENERAL INFORMATIONThe System Sensor RTS151KEYA is an automatic fire detector accessorydesigned to test remotely located duct and beam detectors. For 4-wire detec-tors, the RTS151KEYA features a multi-colored LED that alternates betweensteady green and red. Green indicates power and that the detector board isin place. Red indicates alarm. For 2-wire detectors, the LED will show red foralarm. Consult the detector installation instructions for additional information.The National Fire Protection Association and CAN/ULC-S536 has publishedcodes, standards, and recommended practices for the installation and useof this product. It is recommended that the installer be familiar with these re-quirements, with local codes, and any special requirements of the local au-thority having jurisdiction.RTS151KEYA CONTENTS1 RTS151KEYA remote test station1 screw pack (2 mounting screws)2 KeysOPERATIONTest FunctionInsert the key and turn clockwise to the “TEST” position.Alarm IndicationWith the key in the “TEST” position, some time will elapse (40 seconds maxi-mum) depending on the detector type, before the alarm indicating LED willturn red.Reset FunctionTurn the key counterclockwise to the “RESET” position and hold. The LEDshould turn off. Then, turn the key back to the “NORMAL” position and re-move. The RTS151KEYA is capable of resetting only certain models of detec-tors. Refer to the detector installation instructions for additional information.Wiring InstructionsConsult the appropriate detector installation instructions for the applicablewiring diagram. The RTS151KEYA mounts to a single gang box (2 1/2˝ mini-mum depth), or directly to the wall or ceiling.In Canadian applications, the RTS151KEYA is intended to be located in thesame room as the smoke detector and within 60 feet of the unit.OFFRESET TESTH0195-01H0582-13FIGURE 1. RTS151KEYAFIGURE 2: WIRING DIAGRAM FOR RTS151KEYA TO D4120A4-WIRE DUCT SMOKE DETECTOR:FIGURE 3: WIRING DIAGRAM FOR RTS151KEYA TO D2A 2-WIREDUCT SMOKE DETECTOR:SPECIFICATIONSDimensions: 4.6˝ H × 2.75˝ W × 1.8˝ DWeight: 0.24 Lbs.Power RequirementsPower LED (Green): 14 – 35 VDC, 12 mA maximumAlarm LED (Red): 2.8 – 32 VDC, 12 mA maximumAlarm Response Time: 40 seconds maximumTemperature: –10°C to 60°C (14°F to 140°F)Humidity: 95% relative humidity, noncondensing Max261543D4120ARTS151KEYA(GREEN LED)POWER(RED LED)ALARMFIELDINSTALLEDJUMPERAUX OUT +AUX OUT –ALARMR TESTR RESETSUP, NOSUP, C* Sup. contacts cannot be used if they are wired to control panel.*EXTERNAL(-) POWER (+)SUPPLY*RTS151KEYAREMOTE TEST STATIONLED OPTION1 PER UNIT10mA CURRENT DRAWTEST COIL OPTION1 PER UNIT95mA CURRENT DRAW4 5321TEST COIL +TEST COIL –COMM +OUT (CONV ONLY) +COMM –RA/RTS –RA +RTS +NOTE: THE RTS151KEYA TEST COILCIRCUIT REQUIRES AN EXTERNAL 24 VDCPOWER SUPPLY WHICH MUST BE UL LISTED.NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THEINSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL,SOLD SEPARATELY.H0571-10