5.5.2 ID control commands# Commands1 :MDL?;2 :REV?;DescriptionReturns the power supply model identification as an ASCII string:Nemic-Lambda ZUP(XXV)-(YYA).XX - The rated output voltageYY - The rated output currentexample: Nemic-Lambda ZUP(6V-33A)Returns the software version as an ASCII string:Ver XX-YYA.BXX- The rated output voltageYY- The rated output currentA.B- Version identifierexample: Ver 6-33 1.05.5.1 Initialization control# Commands2 :DCL;1 :ADRn;3 :RMTn;4 :RMT?;DescriptionClears the communication buffer and the following registers:1. Operational status register2. Alarm (fault) status register3. Programming error registerSets the power supply address. ADR is followed by the addresswhich can be 01 to 31.Sets the power supply to local or remote mode. (This command is activewhen the unit is either in Local or Remote modes).Transition from Local toRemote mode is made via the front panel only.:RMT0; Transition from Remote to Local mode.:RMT1; Transition from latched Remote to non-latched Remote.:RMT2; Latched remote: Transition back to Local mode or to non- latchedRemote can be made via the serial port (RS232/485).At this mode, the front panel Local/Rem function is disabled. Escape fromthis mode to non -latched remote mode can be made by turning the ACON/OFF to OFF and after approx. 10sec.to ON again.Returns the remote/local setting. The returned data is an ASCII string.RM1 (The unit is in remote mode)RM2 (The unit is in latched remote mode)