5.5.3 Output control# Commands1 :VOLn;2 :VOL!;DescriptionSets the output voltage value in volts. This programmed voltage is theactual output at constant-voltage mode or the voltage limit at constantcurrent mode. The range of the voltage values are as shown in table 5-1.Use all digits for voltage programmingReturns the string (Set Voltage) followed by the present programmedoutput voltage value. The actual voltage range is as shown in table 5-1.example: SV5.010 SV08.500SVNote:The ZUP can accept programmed valuehigher by up to 5% than the table values,however it is not recommended to programpower supply over the rated voltage.Table 5-1: Voltage programming range.Example - ZUP6-XY :VOL5.010; ZUP10-XY :VOL08.500;Example - ZUP60-3.5 :CUR3.000; ZUP10-40 :CUR07.50;Model MIN. MAX.ZUP6-XY 0.000 6.000ZUP10-XY 00.000 10.000ZUP20-XY 00.000 20.000ZUP36-XYZUP80-XY00.0000.0036.0080.00ZUP60-XYZUP120-XY00.00000.0060.00120.004 :CURn;3 :VOL?;Sets the output current in Ampers. This programmed current is the actualoutput current at constant-current mode or the current limit at constantvoltage mode. The programming range is shown in table 5-2:Use all digits for current programming.Returns the string (Actual Voltage) followed by the actual output voltage.The actual voltage range is the same as the programming range.example: AV5.010 AV08.500AVNote:The ZUP can accept values higher by 5%than the rating. It is recommended to set theoutput current to 105% of the rating if theunit is required to supply the rated current.Model MIN. MAX.ZUP6-33 00.00 33.00ZUP6-66 00.00 66.00ZUP6-132 000.00 132.00ZUP10-20 00.000 20.000ZUP10-40ZUP10-80ZUP20-10ZUP20-20ZUP20-40ZUP36-6ZUP36-1200.0000.0000.00000.00000.000.00000.00040.0080.0010.00020.00040.006.00012.000ZUP36-24ZUP60-3.5ZUP60-7ZUP60-1400.0000.0000.00000.00024.0003.5007.00014.000ZUP80-2.5ZUP80-5ZUP120-1.8ZUP120-3.60.00000.0000.00000.0002.50005.0001.80003.600Table 5-2: Current programming range.