UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13 4-34: OperationON/OFF Start-up and shutdown buttonsThe UPS may be switched ON or OFF by simultaneously pressing both ON/OFF keys on the control panel.This is to prevent accidental UPS start-up or shutdown.Note: When the UPS is under normal operation, pressing the two ON/OFF buttons simultaneously willimmediately shut down the UPS and disconnect the UPS from the load.4.3 Description of the LCD display4.3.1 Status screens4.3.2 Main menu screenCAUTION: If theON/OFF buttons are operated while the UPS is not in Maintenance Bypass itwill interrupt the load power supply.DESCRIPTION LCD-DISPLAY1. Load is protected by UPS power supplied by inverter (normal operation). LOADPROTECTED2. Load is not protected by UPS power –supplied by mains power (load onbypass)LOADNOT PROTECTED3. Load supply interrupted. UPS has been switched off by “ON/OFF”buttons.LOAD OFFSUPPLY FAILURE4. The UPS/module is not supplying load.The output switch is open.LOAD DISCONNECTEDOUTPUT SWITCH OPENDESCRIPTION LCD-DISPLAY1. A log of the last 64 events is stored in the Power Management Display(See paragraph 4.3.3).→ EVENT LOGMEASUREMENTS2. Allows monitoring of voltages, power, frequencies, currents, autonomyetc (See paragraph 4.3.4)→ MEASUREMENTSCOMMANDS3. Enables the commands “Load to inverter”, “Load to bypass” and batterytest to be executed (See paragraph 4.3.5).→ COMMANDSSET-UP DATA4. Allows the UPS personalized information (such as serial number) to beentered (See paragraph 4.3.6).→ SET-UP DATASET-UP USER5. Allows user to set up Date/Time, automatic battery test, etc.(See paragraph 4.3.7)→ SET-UP USERSET-UP SERVICE6. Password-protected area for service engineer use only (See paragraph4.3.8).→ SET-UP SERVICE