DSBA2300 rév.31-10-06 10/23Electric connection GBInput signal Output signal Schunt K1 Schunt K2 Schunt K3A B A B0-10V 0-10V ON OFF ON OFF OFF0-10V 0-20mA ON OFF OFF ON OFF0-10V 4-20mA ON OFF OFF ON ON0-20mA 0-10V OFF ON ON OFF OFF0-20mA 0-20mA OFF ON OFF ON OFF0-20mA 4-20mA OFF ON OFF ON ON4-20mA 0-10v OFF ON ON OFF OFF4-20mA 0-20mA OFF ON OFF ON OFF4-20mA 4-20mA OFF ON OFF ON ONGRRRRG RRRGGPARAMETER SELECTION SEQUENCE1 Selection of the flow direction of the valve1.1 Normal flow direction (by default)- Press the OPEN button and apply the operating voltage to the card while keeping this button depressed.- The green LED lights up. Release the OPEN button.- Disconnect the card.1.2 Inverse flow direction- Press the CLOSE button and apply the operating voltage to the card while keeping this button depressed .- The red LED lights up. Release the CLOSE button.- Disconnect the card.2 Selection of the type of set value2.1 Voltage set value 0-10V- Press the MEM button and apply the operating voltage to the card while keeping this button depressed.- The red LED will light up 3 times. Release this button.- Disconnect the card.2.2 Current set value 0-20mA- Press the MEM and OPEN buttons and apply the operating voltage to the card while keeping these but-tons depressed.- The red LED will light up 3 times. Release these buttons.- Disconnect the card.2.3 Current set value 4-20mA (by default)- Press the MEM and CLOSE buttons and apply the operating voltage to the card while keeping these but-tons depressed.- The red LED will light up 3 times. Release these buttons.- Disconnect the card.3 Learning mode- Press the OPEN and CLOSE buttons and apply the operating voltage to the card while keeping these but-tons depressed.- The 2 LEDs will light up. Release these buttons and the 2 LEDs will extinguish. The card is now in thelearning mode.- Press the CLOSE button to put the valve in its closed position. The red LED will light up.- Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 3 times as aconfirmation of acknowledgement.- Press the OPEN button to put the valve in its open position. The green LED will light up.- Store this selected open position by pushing MEM + OPEN, the green LED will light up 3 times as aconfirmation of acknowledgement.- Now, the positions selected have been stored. Disconnect the card.4 Shunts positioning K1, K2 and K3- Position the shunts as follows (before modification, switch off the card) :NORMAL OPERATING MODE- Apply the operating voltage to the card. The green LED will light up 3 times.- Under normal operating conditions, the green LED will light up when the drive motor opens the valve, andthe red LED will light up when the drive motor closes it.- If both LEDs remain extinguished, it means that the drive motor has not been triggered.- In the case of an over torque, the motor stops and the 2 LEDS lights then together to indicatethe action of the torque limiter. To re-start it, you must either reverse the sense of rotation, eitherswitch the power off and on.GG RK3 ONK3 OFFOFF ON