2* Setting internal parameters.Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset,setpoint range and the functions of the thermostat.Push the DOWN key more than 10 seconds, to enter the 'Internal Programming Menu'. In the leftdisplay the upper and lower segment are blinking. Over the UP and DOWN keys the requiredparameter can be selected (see table for the parameters).If the required parameter is selected, the value can be read-out by pushing the SET key. Pushingthe UP or DOWN key to change the value of this parameter.If after 20 seconds no key is pushed, the ALFANET 71 changes to the normal operation mode.* Adjustment sensors.Sensor-1 can be adjusted by using the Sensor Offset parameter 06 and Sensor-2 can be adjustedby using the Sensor Offset parameter 07. Indicates a Sensor e.g. 2°C to much, the accordingSensor Offset has to be decreased with 2°C.* Error messages.In the display of the ALFANET 71 the following error messages can appear:LO - Minimum alarm. Solution E1,E2:HI - Maximum alarm. - Check if the sensor is connected correctly.E1 - Sensor-1 failure. - Check sensor (1000Ω at 25°C).E2 - Sensor-2 failure. - Replace sensor.EEE - Settings are lost. Solution EEE:- Reprogram the settings.-L- - In case of sensor short-circuit the display alternates between error-code E..and -L-, as indication for a short-circuit sensor.-H- - In case of open-circuit sensor the display alternates between error-code E..and -H-, as indication for a open circuit sensor.Reset Alarm.When a error-messages appears it can be resetted by pushing the SET key. Thefunction of this key depends on parameter P37.* Technical details.Type : ALFANET 71 ThermostatRange : -50/+50,0°C, above -10°C display per 0,1°CSupply : 12Vac 50/60Hz (-5/+10%)Display : 3-digit 7-segment displayRelays : Ry1= SPST(NO) 250V/8A (cos φ=1) of 250V/5A (cos φ=0.4)Ry2= SPST(NO) 250V/8A (cos φ=1) of 250V/5A (cos φ=0.4)Ry3= SPDT(NO/NC) 250V/8A (cos φ=1) of 250V/5A (cos φ=0.4)Relays have one common (C).Control : By push buttons on front.Front : Polycarbonate IP65Sensors : 2x SM 811/2m (PTC 1000Ω/25°C).Communication : RS485-Network (2-wire shielded cable min. 0,75mm2)Dimensions : 35 x 77 x 71,5mm (HWD)Panel cutout : 28 x 70mm (HW)Accuracy : ± 0,5% of the range.- Provided with memory protection during power failure.- Connections with screw terminals on the back side.- Equipped with sensor failure detection.- Special versions on request available.