9vacon • 76 APPENDIX 1 - VENDOR CONTROL AND STATUS WORD DESCRIPTIONSTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2059.2 FBFixedStatusWord and FBGeneralStatusWordThe Status word is composed of 32 bits. FBFixedStatusWord consist of the first 16 bits. FBGen-eralStatusWord consist of the remaining 16 bits. While the functionality of FBFixedStatusWord isfixed in the VACON® standard applications, the functionality of FBGeneralStatusWord is totallyapplication specific and can vary even in the VACON® standard applications.The meanings of FBFixedStatusWord bits are described below. Unused bits have to be set to zero.B10 Jogging 1 0 No action.1 Jogging request with ref1.B11 Jogging 2 0 No action.1 Jogging request with ref2.B12 Quick stop 0 Drive operates as normal.1 Drive executes quick stop / emergency stop.B13 Reserved 0 -1 -B14 Reserved 0 -1 -B15 Reserved 0 -1 -Table 79. FBFixedStatusWord bitsBit Function DescriptionB0 Ready 0 Drive is not ready.1 Drive is ready to run.B1 Run 0 Motor is not running.1 Motor is running.B2 Direction 0 Motor is running clockwise.1 Motor is running counterclockwise.B3 Fault 0 No fault active.1 Drive has an active fault.B4 Alarm 0 No alarm active.1 Drive has active alarm.B5 At reference 0 Motor is not running at reference speed.1 Motor is running at reference speed.B6 Zero speed 0 Motor is not at zero speed.1 Motor is running at zero speed.B7 Flux ready 0 Motor is not magnetized.1 Motor is magnetized.B8-B12 ReservedTable 78. FBFixedControlWord bitsBit Function Description