9 TECHNICAL DATA, VACON® 100 FLOW9.1 AC DRIVE POWER RATINGS9.1.1 MAINS VOLTAGE 380-500 VTable 31: The power ratings of Vacon® 100 FLOW in mains voltage 380-500 V, 50-60 Hz, 3~Frame Drive type Loadability Motor shaft powerContinuouscurrentILout [A]Inputcurrent ILin[A]10%overloadcurrent [A]Maxcurrent IS2s400 Vmains480 Vmains10%overload40°C [kW]10%overload40°C [hp]MR8 0140 140.0 139.4 154.0 210.0 75.0 100.00170 170.0 166.5 187.0 280.0 90.0 125.00205 205.0 199.6 225.5 340.0 110.0 150.0MR9 0261 261.0 258.0 287.1 410.0 132.0 200.00310 310.0 303.0 341.0 502.0 160.0 250.0MR10 0385 385.0 385.0 423.5 620.0 200.0 300.00460 460.0 460.0 506.0 770.0 250.0 350.00520 520.0 520.0 572.0 920.0 250.0 450.00590* 590.0 590.0 649.0 1040.0 315.0 500.0MR12 0650 650.0 648.0 715.0 1180.0 355.0 500.00730 730.0 724.0 803.0 1300.0 400.0 600.00820 820.0 822.0 902.0 1460.0 450.0 700.00920 920.0 916.0 1012.0 1640.0 500.0 800.01040* 1040.0 1030.0 1144.0 1840.0 560.0 900.01180* 1180.0 1164.0 1298.0 1840.0 630.0 1000.0* = The maximum ambient temperature is 35°C with the du/dt filter option. These currentsare not available when you have the options back channel cooling and du/dt filter (+CHCBand +PODU).VACON · 104 TECHNICAL DATA, VACON® 100 FLOW9 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205