9vacon • 49 AnnexTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2059. ANNEXProcess Data IN (Master to Slave)Use of Process Data In variables depends on the used application. The configuration of the datais free.Process Data OUT (Slave to Master)Use of Process Data Out variables depends on the used application.The Fieldbus Master can read the frequency converter’s actual values using process data vari-ables. Control applications use process data as follows:Table 32. Process Data OUT variablesNote 1: In Vacon®100, the Motor Current scale depends on the drive size. In Vacon 100 HVACthe Motor Current scale is always 0.1 A.Note 2: In Vacon 100 HVAC, the default ID is 45 meaning "Motor Current 1 Decimal". In Vacon100, the default ID is 3 for Motor Current. The ID 45 can be mapped by the user to this variablealso in Vacon 100.Register Data Default ID Information Unit2104 Process data OUT 1 1 Output Frequency 0,01 Hz2105 Process data OUT 2 2 Motor Speed 1 rpm2106 Process data OUT 3 3(45) 2 Motor Current 0,1 A2107 Process data OUT 4 4 Motor Torque 0,1 %2108 Process data OUT 5 5 Motor Power 0,1 %2109 Process data OUT 6 6 Motor Voltage 0,1 V2110 Process data OUT 7 7 DC link voltage 1 V2111 Process data OUT 8 37 Active Fault Code -