Commissioning vacon • 1124-hour support +358 (0)201 212 575 • Email: vacon@vacon.com4Figure 6.Configuration example from EIPScan tool.4.1 Parameters4.1.1 Protocol in useWhen value is changed to one, protocol stack is activated.Please notice that if protocol is stopped (for example protocol is set to zero from panel) and com-munications have been open, it might be that stack cannot be reinitialized during the next few min-Table 2. Parameters Menu# Name DefaultRange /AcceptedValuesID Definition1 Protocol In Use 0 0…1 2417d 0 = protocol not in use.2Output Instance 21 20, 21, 23,101, 111,128, 1312418 d See chapter Assembly InstancesImplemented By Vacon® 1003Input Instance 71 70, 71, 73,107, 117,127, 1372419 d See chapter Assembly InstancesImplemented By Vacon® 1004Communication Timeout 10 0…65535 2420 d 0 = timeout is defined by the mas-ter through Requested PacketInterval (RPI) multiplied by Con-nection Timeout Multiplier (CTM).Other value than 0 means thetotal time (in seconds) includingthe RPI x CTM timeout