Startup vacon • 22Service support: find your nearest Vacon service center at www.vacon.com33.2.6 Motor potentiometer applicationUse the Motor potentiometer application for the processes where the frequency reference ofthe motor is controlled (that is, increased and decreased) through digital inputs.In this application, the I/O terminal is set to the default control place. the start/stop commandsare given with DI1 and DI2. The frequency reference of the motor is increased with DI5 and de-creased with DI6.It is possible to configure all the drive outputs freely in all the applications. There are 1 ana-logue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basicI/O board.3.2.6.1 M1.36 Motor PotentiomTable 7. Motor Potentiom start-up wizard menuCode Parameter Min Max Unit Default ID DescriptionP1.36.1 MotPot ramp time 0.1 500.0 Hz/s 10.0 331Rate of change in the motorpotentiometer referencewhen increased ordecreased with parametersP3.3.4.1 or P3.3.4.2.P1.36.2 MotPot Reset 0 2 1 367Motor potentiometer fre-quency reference resetlogic.0 = No reset1 = Reset if stopped2 = Reset if powered downP1.36.3 Preset Freq 1 P1.3 P1.4 Hz 20.0 105Make the selection of apreset frequency withthe digital input DI4and DI5.