Split Type Installation Manual145 Temperature by CapacitiesCOOLING OUTDOOR TEMPERATURE DRYIndoorConditions 21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC21ºC D15ºC WTotal capacity- kW 6,16 6,13 6,11 5,94 5,71 5,19 4,66Sensitive capacity- kW 4,90 4,89 4,87 4,74 4,57 4,18 3,79Input- kW 1,57 1,67 1,77 1,93 1,88 1,82 1,7724ºC D17ºC WTotal capacity- kW 6,48 6,48 6,44 6,24 6,00 5,47 4,93Sensitive capacity- kW 5,15 5,15 5,12 4,97 4,79 4,39 3,98Input- kW 2,44 2,43 2,42 4,54 2,24 2,03 1,8127ºC D19ºC WTotal capacity- kW 6,84 6,81 6,77 6,55 6,31 5,76 5,19Sensitive capacity- kW 5,42 5,40 5,36 5,20 5,02 4,61 4,18Input- kW 1,77 1,88 2,00 2,18 2,13 2,08 2,0332ºC D23ºC WTotal capacity- kW 7,39 7,38 7,32 7,03 6,79 6,24 5,63Sensitive capacity- kW 5,83 5,82 5,78 5,56 5,38 4,97 4,51Input- kW 1,93 2,08 2,21 2,38 2,31 2,28 2,23Table 5.9 Cooling temperarures.5.5 V12-060 M2WHEATING OUTDOOR TEMPERATURE DRYIndoorConditions24ºC D18ºC W12ºC D11ºC W7ºC D6ºC W4ºC D3ºC W0ºC D-1ºC W-5ºC D-6ºC W-7C D-8ºC W-15ºC D-16ºC W15ºC Capacity- kW 7,91 5,04 4,68 5,83 5,45 5,29 5,22 5,15Input- kW 2,25 2,31 2,38 2,20 2,14 2,07 2,03 1,9218ºC Capacity- kW 7,68 6,31 5,94 5,65 5,29 5,11 5,06 4,93Input- kW 2,12 2,20 2,25 2,07 2,03 1,96 1,92 1,8320ºC Capacity- kW 7,54 7,16 6,95 5,54 5,18 4,97 4,93 4,77Input- kW 2,05 2,12 2,16 2,01 1,94 1,90 1,85 1,7722ºC Capacity- kW 7,43 7,07 6,71 5,45 5,09 4,90 4,86 4,72Input- kW 2,09 2,18 2,24 2,05 2,01 1,94 1,90 1,8127ºC Capacity- kW 7,18 6,82 6,48 5,27 4,88 4,72 4,70 4,57Input- kW 2,23 2,29 2,36 2,18 2,12 2,05 2,01 1,90Table 5.10 Heating temperarures.