Instructions for Use, Installation and Servicing ecoMAX pro3416 Fault finding16.3 Fault CodesFault codes take priority over all other display functionsin the event of a system fault occurring.Code Description CommentF1 Ignition fault (lockout) No gas; Insufficient gas; Incorrect gas valve adjustment; Electrode defect;Failed to light Ignition lead defect; Electronic igniter defective; Check air inlet duct;Check connections to igniter unitF4 Ignition fault (lockout) As aboveWent out when litF5 Overheat fault Overheat stat operated; Maximum temperature exceeded;Check thermistor connections; Air in system with thermistor at maximumsetting; Faulty overheat stat connection; Check that pump is wired intoappliance and not from programmer. This would cause no pump overrunF6 Central heating flow NTC fault Flow NTC cable defective/broken NTC faultyFlow thermistor not fitted correctly, Check pipe work configurationF10 Central heating return NTC fault Return NTC cable defective/broken NTC faultyCheck that thermistor attached correctly to pipe.F11 No reception by main board Connection fault between main PCB and interface; Faulty interface;Faulty main PCB (processor), Check fanF12 No reception by the local user interface As F.11F13 Main board fault As F.11F14 Central heating flow t° > 95° C System fault; Possible external pump failure; Check NTC on flowCheck that pump is wired into appliance and not from programmer.This would cause no pump overrunF16 Flame detection fault(flame presence >5 s after burner stop) Gas valve defectiveF17 Power supply <170 V Check electrical supply / polarity, Check fanF18 Local user interface fault Connections; Faulty interfaceF19 Central heating NTC unplugged Check NTC connectionF20 MMI software incompatible with IRIS software Possible connection faultF24 Central heating return t° >90°C System fault; Possible external pump failure; Check NTC on return;Check that pump is wired into appliance and not from programmer.This would cause no pump overrun.F25 Maximum temperature rise slope Possible external pump failure; Air in system restricting movement of water.Insufficient circuit flowF26 Maximum delta t Check NTC on return; System fault – too restrictive?; Possible pump failure16.2 Fault MemoryThe fault memory stores details of the five most recentfaults. To display the fault memory, proceed as follows;• With the interface in ‘normal’ mode, press and hold the‘mode’ button ( ) for 10 seconds until a flashing ‘0’appears.• Press the ‘mode’ button again.• The 5 fault memory screens are now available to beviewed, memory 1 being the most recent. Within eachmemory screen, 5 additional screens provide furtherinformation to assist the installer/engineer.To cancel the fault memory mode proceed as follows;• Press and hold the ‘mode’ button for 10 seconds untilthe screen returns to the ‘user’ mode.No. Memory screen type Comments1 Fault code Fault code 1 – 26 (see page 34 – ‘Fault finding’)2 Burner phase Working phase3 DHW temperature No function4 CH flow temperature °C at time of fault5 Tank temperature No function