81Installation instructions geoTHERM VWS/VWW 0020051574_01Description Unit VWS 220/2 VWS 300/2 VWS 380/2 VWS 460/2Heat pump performance dataB0W35 dT5- Heating output- Power consumption- Performance figure/COPB0W35 dT10- Heating output- Power consumption- Performance figure/COPkWkW-kWkW-21,65.14.322,14.94.529,96.84.430,56,54.738,38,84.438,78,44.645,910,64.445,510,14.5Performance data, heat pump (contd.)B5W55- Heating output- Power consumption- Performance figure/COP-kWkW-23,07,03.331,59,63.341,112,33.448,614,73.3Internal sound level dBA 63 63 63 65Conforms to safety regulations - CE 1027 markLow Voltage Directive 73/23/EWGEMC Directive 89/336/EWGEN 60335ISO 5149Pressure equipment directive 97/23/EC, category IITable 13.1 Technical data - VWS (cont)a Caution!407 C is a chlorine-free coolant whichdoes not affect the ozone layer.Nevertheless, any servicing work on thecoolant circuit should only be carried outby authorised specialists.13.2 Technical Data VWWDescription Unit VWW 220/2 VWW 300/2 VWW 380/2 VWW 460/2Article number - 0010002801 0010002802 0010002803 0010002804Height without connectionsWidthDepth without pillarsDepth with pillarsmmmmmmmm12007609001100Weight- With packaging- Without packaging- Ready for operationkgkgkg340310325354324343374344366397367394Rated voltage- Compressor- External well pump- External heating circuit pump- Control circuit- External auxiliary heating-3/N/PE 400 V 50 Hz3/N/PE 400 V 50 Hz (max. 3 x 5 A) 3/N/PE 400 V 50 Hz (max. 3 x 8.5 A)1/N/PE 230 V 50 Hz (max. 1 x 2 A)1/N/PE 230 V 50 Hz3/N/PE 400 V 50 Hz (max. 3 x 13 A)Fuse, slow-blow A 20 25 32 40Start-up current- Without start-up current limiter- With start-up current limiterAA99441276516785198110Electrical power consumption/rated output- Min. for B-5W35- Max. for B20W60- Phase angle, cos phikWkW-4.910,00,7-0,846.612,00,72-0,838.516,00,76-0,8610,218,00,75-0,86- External auxiliary heating kW 3 x 3 (3 x 13A)EN 60529 level of protection - IP 20Table 13.2 Technical data - VWWTechnical data 13