Dispenser Pan Sensor Testing Installing the Dispenser Pan Sensor163. Install the mounting hardware according to the dispenser pan manufacturer’sinstructions.Important ☞ Mounting hardware should be ordered from the dispenser pan manufacturer. Specifythat you are installing a Veeder-Root Dispenser Pan Sensor when ordering from the panmanufacturer. An optional Veeder-Root Universal Mounting Kit (No. 330020-012) isavailable.4. Secure the mounting bracket in the dispenser pan and slide the sensor into position.5. Connect the cable from the Dispenser Control Interface to the sensor and secure thecable nut.Important ☞ For proper sensor operation, sensor connector and cable interface must be dry and freefrom any contaminants.6. Tighten the cord grip nut to ensure a watertight seal at the cable entry.7. Restore AC power to the junction box.Dispenser Pan Sensor TestingAfter sensor installation, test each dispenser pan sensor with dispenser interfaceinstalled to be sure it is working properly:1. To test the sensor, turn the sensor upside-down. The dispenser should be disabled.Important ☞ If the dispenser is not disabled during the test, review the installation instructions in“Dispenser Control Interface Installation” on page 5. If the sensor does not deactivateafter you review the installation, contact your Veeder-Root representative or distributor.2. To reactivate the dispenser, turn the dispenser power OFF for at least 15 seconds,then turn it back ON.Important ☞ Final approval of a field installation of this product into an existing dispenser is underthe authority of the local inspector.