Setup PMC SetupPMC SetupFigure 3 diagrams the PMC setup programming.Figure 3. PMC SetupPMC SETUPPRESS TO CONTINUESETUP MODEPRESS TO CONTVAPOR PROCESSORMAX RUNTIME MINUTES: 60 Prints out a copy of thePMC Setup entries. Seeexample at right.MPSSFTURN OFF VAPOR PROCESSORINCHES WC: -0.200Range checking is enforced:280Default: 60 minutesS TURN ON VAPOR PROCESSORINCHES WC: +0.200S HYDROCARBON SELECTPRESS Use key to make selectionMODBUS Sensor default enabledS OVER PRESSURE LIMITINCHES WC: xx.xxRange checking is enforced:0 < xx.xx < 3.5Default: 0.0S DUTY CYCLE LIMITxx.xx %Range checking is enforced:0 < xx.xx < 100Default: 75%Use key to enter.Default Start time = 11:59 PMUse key to enter.0< delay < =720Default:= 001NOTE: If delay minutes =0, the results will be posted as soon asthey become available, else mmm minutes after start time.Data collected 5 minutes before the Start of Test time is omittedfrom test.S SET ANALYSIS TIMEPRESS ESSET TEST START TIMETIME: hh:mmSET POST DELAY DURATIONDELAY MINUTES: mmmisd\pmc-1.epsCFPSTChangeE EnterFunctionPrintM ModeStepTank/SensorKey presssequenceRepress untildesired messageappears in displayKey Legend1 2PMC SETUP----------------------PMC VERSION: 01.00VAPOR PROCESSOR TYPEVST VAPOR PROCESSORMAX RUNTIME MINUTES: 90ON: -0.200 INCHESOFF:-0.600 INCHESEFFLUENT EMISSIONS LIMIT0.649 LB/1KGOVER PRESSURE LIMITxx.xx PERCENT%DUTY CYCLE LIMITxx.xx PRECENT%ANALYSIS TIMESTIME 11:59 PMDELAY MINUTES 1+30+0.2 Turn Onvapor processorUllage vapor pressureTurn Offvapor processor-0.2-8AbsoluteRange(IWC)P/V valve opens Vapor ProcessorOn/Off exampleSets vapor processor Off point. Range:-8 < Off setting < On setting. For moreinformation see example at right.Sets vapor processor On point. Range:Off setting < On setting < +3. For moreinformation see example at right.NOTE: This menu is not used.Section 16Pressure Management Control16-6