5-115 Warning and Alarm Messages Displayed Alarm MessagesTable 5-17. Contact AlarmsAlarm Cause ActionAutodial Failed Alarm System failed to connect to a remotereceiver after ‘n’ tries.Verify the address book settings for the con-tact are correct (i.e., modem device number,phone number to dial), verify the receivingdevice (fax or modem) is operational. Con-tact technical support for assistance.Autodial Setup Data Warning Device setup data problem Recheck device setup parameters.Email Failed The console did not successfully sendemail when configured to email.Verify the address book settings for the con-tact are correct (email address of recipient),verify network connectivity is available(Ethernet card is installed). Contact techni-cal support for assistance.Fax Failed The console did not successfully sendfax when configured to fax. Verify the address book settings for the con-tact are correct (fax address of recipient),verify modem is configured. Contact techni-cal support for assistance.Table 5-18. Auto Events AlarmsAlarm Cause ActionSetup Data Warning Device setup data problem Recheck device setup parameters.Table 5-19. Product AlarmsAlarm Cause ActionProduct Setup Warning Setup is incomplete or in error. Meter Data Present not setup. Tempera-ture Compensation not setup. BIR AlarmThreshold and/or Alarm Offset valuesincorrect.Product Threshold Alarm Periodic variance exceeds threshold. The periodic variance of a productexceeded the BIR calculated threshold.Table 5-20. DIM AlarmsAlarm Cause ActionCommunication FailureAlarmDIM module has stopped communicating with theexternal equipment or the cable adaptor box.Reconnect the external equipment oradaptor box to the TLS.Disabled DIM DIM module has stopped communicating with centralprocessing unit of the console.Verify DIM firmware is correct.Replace DIM module.Setup Data Warning Device setup data problem Recheck device setup parameters.