11 CSLD Troubleshooting Static Leak Test11-124. Defective probe.5. Not enough idle time (see message above).6. Tests are being rejected because the test results indicate a rate increase >+0.4 gph.Static Leak TestIf after troubleshooting the Periodic Leak Test Fail Alarm an equipment problem has not been identified, perform astatic leak test. Be sure that the product pump cannot come on during the test and that the level in the tank iswithin the normal operating range (i.e., the results of the static test may not be meaningful if the tank is nearlyempty). If the static test verifies the CSLD result follow the procedures as established by the site owner. If thestatic test passes, contact Technical Support for assistance.When to Manually Clear the CSLD Rate TableYou should manually clear the CSLD Rate Table if data, known to be inaccurate, had been stored in the table andthe source of the inaccurate data was subsequently removed (e.g., after making tank plumbing repairs).The CSLD Rate Table can be cleared by touching the Clear Table button on the CSLD Rate Table tab screen, orvia the RS-232 command shown below.IMPORTANT! DO NOT CLEAR THE CSLD RATE TABLE UNLESS IT IS ABSOLUTELY NECESSARY.DATA CLEARED FROM THIS TABLE CAN NOT BE RECOVERED!Function Code: 054Function Type: Delete CSLD Rate TableCommand Format:Display: S054TT149Computer: s054TT149NOTE:1. TT - Tank number (command valid for single tank only).2. 149 - Verification code.Typical Response Message Display:S05402149JAN 1, 1997 8:03 AMT2:PRODUCT 2 CSLD RECORDS DELETEDtypical Response Message Computer:s054TTYYMMDDHHMM&&CCCCNOTE:1. YYMMDDHHmm - Current time of day2. TT - Tank number3. && - Data termination flag4. CCCC - Message checksum.