Setup Output Relay Setup - VST ECS Membrane Processor & VST Green Machine8Output Relay Setup - VST ECS Membrane Processor & VST Green MachineThe Output Relay setup programs an output relay so that the TLS console can switch a controlled vapor processoron and off as shown in Figure 4.Figure 4. Output Relay Setup for VST ECS Membrane ProcessorFigure 5 shows example setup printouts of the Output Relays setup.Figure 5. Output Relay Setup Printout Examples for TLS Console Controlled ProcessorSETUP MODEPRESS TO CONTOUTPUT RELAY SETUPPRESS TO CONTINUEPrints out a copy of the Output Relay Setup entries. See examples in figure below.In our example R1 is the relay used by PMC to control the processor, R2 is the relayused to shutoff the processor when the High Product Alarm is active.MPSSSFENTER RELAY DESIGNATIONR1 :R1 : SELECT RELAY TYPESTANDARDR2 : SELECT RELAY TYPESTANDARDR2 : SELECT TANKNONER1 : SELECT ORIENTATIONNORMALLY OPENR2 : SELECT ORIENTATIONNORMALLY OPENR2 : VP SHUTOFFIN-TANK ALARMS: NOPress Changeand enterVAPOR PROCESSORfor the relayNote: If using an I/OCombo Modulethere are just 2 slots.801-6.epsC Press Changeand enterVP SHUTOFFfor the relayCCE SE SE SRELAY CONFIG - MODULE XSLOT # — X, X, X, XTENTER RELAY DESIGNATIONR2 :SSCE SVapor ProcessorStandardC E SStandardVapor ProcessorC E SE SNormally OpenNormally ClosedNormally ClosedNormally OpenC E SYESNOR2 : IN-TANK ALARMSHI PRODUCT: NO TANKS C E SALL TANKSNO TANKSC ChangeB BackupM Mode E EnterS StepF Function PrintT P1 2 Key presssequenceRepress untildesired messageappears in displayKey LegendTankSensorPress once andthe 2nd X changesto a 2.C CPress once and the firstposition blinks, pressagain and the X changesto a 1.Press once andthe secondposition blinksOUTPUT RELAY SETUP----------------------R 1: VAPOR PROCESSORTYPE:VAPOR PROCESSORNORMALLY OPEN- NO ALARM ASSIGNMENTS -OUTPUT RELAY SETUP----------------------R 2: VP SHUTOFFTYPE:STANDARDNORMALLY CLOSEDIN-TANK ALARMSALL HIGH PRODUCT ALARMSisd-evr\ortlscntrlvpsetprt.eps