POS App Guide DIM Installation Examples23Gilbarco G-Site™ POS SystemsTLS CONSOLE SOFTWARE REQUIREMENTSTLS-350R with BIR Software Requirements• System software Version 17 (or higher)• DIM software 349634-003C (or later)TLS-450/TLS-450PLUS with BIR Software Requirements• TLS-450 System software Version 2.x (or higher)• TLS-450PLUS System software Version 6.x (or higher)• BIR option required (TLS-450)VEEDER-ROOT HARDWARE REQUIREMENTS (REF. TABLE 2)The following equipment is required to interface the TLS to the G-Site POS:• One Gilbarco Interface Module• One installation kit for each current loopSPECIFIC LIMITATIONSUp to 36 Gilbarco Uni-Hose/MPD fueling positions are supported by the TLS-350R, and up to 72 fuelingpositions are supported by the TLS-450/TLS-450PLUS.In-dispenser credit card readers (CRINDS) are supported.To support a DIM and the TLS-350R, the G-Site must be upgraded to include EMC interface capability. This hasbeen released in the following G-Site versions (EMC Interface capability will be released into the Generic G-Siteversion 6):• Exxon - version 25.0.243• Shell - version 33.1.23• Chevron Canada - version 8.1.10The 331063-xxx installation kit contains two gender mender adapters. One gender mender is used for PC G-SITEapplications while both are used for C-2 G-SITEs. The gender mender adapters are not identical. As shown inFigure 6, be sure to use the correct part at the connection points for your particular installation.WIRING DIAGRAMG-Site wiring examples are shown in Figure 6 below: