6810 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-190320Permissible residual ripple - Non-Ex, Ex-ia instrumentƲ for UN 12 V DC (9.6 V < UB < 14 V) ≤ 0.7 Veff (16 … 400 Hz)Ʋ for UN 24 V DC (18 V < UB < 35 V) ≤ 1.0 Veff (16 … 400 Hz)Load resistorƲ Calculation (UB - Umin)/0.022 AƲ Example - Non-Ex instrument withUB= 24 V DC(24 V - 9.6 V)/0.022 A = 655 ΩPotential connections and electrical separating measures in the instrumentElectronics Not non-floatingReference voltage13) 500 V ACConductive connection Between ground terminal and metallic process fittingElectrical protective measures14)Housing material Version Protection acc. toIEC 60529Protection acc. toNEMAPlasticSingle chamberIP 66/IP 67 Type 4xAluminium IP 66/IP 67IP 66/IP 68 (0.2 bar)Type 4xType 6PStainless steel (electro-polished) IP 66/IP 67IP 69KType 4x-Stainless steel (precision cast-ing)IP 66/IP 67IP 66/IP 68 (0.2 bar)Type 4xType 6PStainless steel Transmitter for external housing IP 68 (25 bar) -Altitude above sea levelƲ by default up to 2000 m (6562 ft)Ʋ with connected overvoltage protectionon the master sensorup to 5000 m (16404 ft)Pollution degree15) 4Protection rating (IEC 61010-1) IIApprovalsInstruments with approvals can have different technical specifications depending on the version.For that reason the associated approval documents of these instruments have to be carefullynoted. They are part of the delivery or can be downloaded under www.vega.com, "Instrumentsearch (serial number)" as well as in the download area.10.2 Calculation of the total deviationThe total deviation of a pressure transmitter indicates the maximum measurement error to be ex-pected in practice. It is also called maximum practical deviation or operational error.13) Galvanic separation between electronics and metal housing parts14) Protection rating IP 66/IP 68 (0.2 bar) only in conjunction with absolute pressure.15) When used with fulfilled housing protection.