155 Set up with the display and adjustment moduleVEGABAR 82 • Slave sensor for electronic differential pressure46332-EN-160212The quick setup for interface measurement is finished.4. Unit, static pressureIn this menu item, you determine the unit of the static, i.e. superim-posed pressure.5. Position correctionIn this menu item you compensate the influence of the installationposition of the instrument (offset) on the measured value.6. DistanceIn this menu item, you enter the installation distance between masterand slave sensor.7. Min. adjustmentIn this menu item you carry out the min. adjustment for level.Enter the percentage value and the corresponding pressure value forthe min. level.8. Max. adjustmentIn this menu item you carry out the max. adjustment for level.Enter the percentage value and the corresponding pressure value forthe max. level.The quick setup for density-compensated level measurement ishence finished.5.2 Parameter adjustment - Extended adjustmentFor technically demanding measuring points, you can carry outextended settings in "Extended adjustment".The main menu is divided into five sections with the following func-tions:Setup: Settings, e.g., for measurement loop name, application, units,position correction, adjustment, signal outputQuick setup - density-compensated level meas-urementMain menu