Note:Screw the housing cover tightly up to the thread stop so that theinspection glass is above the control lamp (LED).To adjust VEGACAP 65, first of all remove the housing cover.You can adapt the switching point to the solid with the potentiometer.With the potentiometer (1) and the measuring range selection switch(2) you can change the sensitivity of the probe to the electricalproperties of the product and the conditions in the vessel. This isnecessary so that the level switch can also reliably detect products e.g. with very low or very high dielectric value.range 1: 0 … 20 pFRange 2: 0 … 85 pFRange 3: 0 … 450 pFWith the mode switch (3) you can change the switching condition ofthe transistor output. You can set the required mode (max. - max.detection or overfill protection, min. - min. detection or dry runprotection).We recommend connecting according to the quiescent currentprinciple (transistor blocks when the switching point is reached)because the transistor output takes on the same (safe) condition if afailure is detected.Control lamp for indication of the switching statusl green = output conductsl red = output blocksl red (flashing) = failureThe adjustment of the switching point is only possible in installedcondition.The specifications in parenthesis refer to the preceding illustration.Vertically mounted probes1 Set mode switch (3) to mode max.2 Set meas. range selection switch (2) to range 1.3 Fill the vessel up to the requested level.4 Turn potentiometer (1) to position 10.When the control lamp (6) lights red: set the measuring rangeselection switch (2) to the next higher measuring range.When the control lamp (6) lights green: continue with the next item.5 Turn the potentiometer (1) very slowly anticlockwise until thecontrol lamp (6) lights red.The measuring system is now ready for operation.Switching point adapta-tion (1)Measuring range selec-tion switch (2)Mode adjustment (3)Signal lamp (6)Switching point adjust-mentMode max.(max. detection)VEGACAP 65 • - transistor (NPN/PNP) 216 Set up30018-EN-090604