406 Set up with the display and adjustment moduleVEGADIS 82 • 4 … 20 mA/HART45300-EN-140506source data as well as the target sensor are displayed. If the data donot match, a failure message is outputted or the function is blocked.The data are only saved after release.In this menu item, you can read out the instrument name and theinstrument serial number.6.8 Parameter adjustment VEGAWELL 52The main menu is divided into four areas with the following functions:Basic adjustment: Settings, for example of the unit of measurement,position correction, adjustment, damping, signal outputDiagnosis: Information, for example, on device status, peak valueService: ResetInfo: Instrument type and serial numberIn this menu item, the adjustment units of the instrument are deter-mined. The selection determines the displayed unit in the menu items"Min. adjustment (zero)" and "Max. adjustment (span)".Unit of measurement:If the level should be adjusted in a height unit, the density of the me-dium must also be entered later during the adjustment.Enter the requested parameters via the appropriate keys, save yoursettings with [OK] and jump to the next menu item with the [ESC] andthe [->] key.The installation position of the instrument can shift the measuredvalue (offset). The position correction compensates this offset. By do-ing so, the actual measured value is taken over automatically.If the actual measured value should be taken over as correction valueduring automatic position correction, this value must not be influ-enced by product coverage or static pressure.With the manual position correction, the offset value can be deter-mined by the user. Select for this purpose the function "Edit" andenter the requested value.Save your settings with [OK] and move with [ESC] and [->] to thenext menu item.Info - Instrument nameMain menuBasic adjustment - Ad-justment unitBasic adjustment - Posi-tion correction