The instrument is adapted to the medium, i.e, the relaydeenergizes when the max. level is reached. Only when themin. probe is decreased, the relay energizes again.Example: A filling pump is switched on when the min. signal isdecreased, fills the vessels until max. signal is reached and isthen switched off.The following settings apply to products with low conductivity(<3 mS)1 Empty the vessel until the min. measuring electrode is onlycovered approx. 1 cm2 Switch on voltage supply3 Set the A/B switch to mode B4 Set the rotary switch to position "TEST max."5 Turn the rotary switch slowly anticlockwise until the redLED lightsThe instrument is adapted to the medium, i.e. the relayenergizes at max. level. Only of the min. probe is decreased,the relay denergizes again.Example: An emptying pump is switched on when the max.signal is reached, empties the vessels until min. signal isreached and is then switched off.In case of several measurement loops (same medium), theadjustment of one instrument with medium is sufficient. Thedetermined switch position can be transferred to all otherinstruments.When the conductivity value is known, the switching pointadjustment can be carried out according to the setup in chart"Rotary switch adjustment".When exchanging the electronics module, it is sufficient to takeover the setting of the old electronics module.6.4 Function chartThe following chart provides an overview of the switchingconditions depending on the adjusted mode and level.Pump control, B modeDry adjustment18 VEGAKON 66 - with relay outputSet up32649-EN-070615