6.3 Parameter adjustmentWith the parameter adjustment, the instrument is adapted to theapplication conditions. The parameter adjustment is carried out via anadjustment menu.Information:In this operating instructions manual, the instrument-specific param-eters are described. Further general parameters are described in theoperating instructions manual "Indicating and adjustment module".The main menu is divided into five areas with the following functions:Setup: Settings, for example, to measurement loop name, medium,application, vessel, adjustment, signal outputDisplay: Language setting, settings for the measured value indicationas well as lightingDiagnosis: Information, for example to the instrument status, pointer,reliability, simulation, echo curveFurther settings: Unit, false signal suppression, linearisation curve,reset, date/time, reset, HART modeInfo: Instrument name, hardware and software version, calibrationdate, instrument featuresIn the main menu point "Setup", the individual submenu points shouldbe selected subsequently and provided with the correct parameters toensure the optimum adjustment of the measurement. The procedure isdescribed in the following.SetupEach medium has different reflection properties. With liquids, furtherinterfering factors are fluctuation product surface and foam generation.With bulk solids, these are dust generation, material cone andadditional echoes from the vessel wall.To adapt the sensor to these different measuring conditions, theselection "Liquid" or "Bulk solid" should be made in this menu item.Main menuSetup/MediumVEGAPULS 62 • 4 … 20 mA/HART two-wire 336 Set up with the indicating and adjustment module36503-EN-100607