569 Diagnosis, asset management and serviceVEGAPULS 69 • HART and accumulator pack47248-EN-180627CodeText messageCause Rectification DevSpecState in CMD 48F260Error in the cali-bration• Error in the calibration carriedout in the factory• Error in the EEPROM• Exchanging the electronics• Send instrument for repairBit 8 of Byte 0 … 5F261Error in the instru-ment settings• Error during setup• False signal suppression faulty• Error when carrying out a reset• Repeat setup• Carry out a resetBit 9 of Byte 0 … 5F264Installation/Setuperror• Adjustment not within the vesselheight/measuring range• Max. measuring range of theinstrument not sufficient• Check or correct installationand/or parameter settings• Use an instrument with biggermeasuring rangeBit 10 of Byte 0 … 5F265Measurement func-tion disturbed• Sensor no longer carries out ameasurement• Operating voltage too low• Check operating voltage• Carry out a reset• Disconnect operating voltagebrieflyBit 11 of Byte 0 … 5Tab. 6: Error codes and text messages, information on causes as well as corrective measures (some specificationsare only valid for four-wire instruments)CodeText messageCause Rectification DevSpecState in CMD 48C700Simulation active• A simulation is active • Finish simulation• Wait for the automatic end after60 mins."Simulation Active"in "StandardizedStatus 0"Tab. 7: Error codes and text messages, information on causes as well as corrective measuresCodeText messageCause Rectification DevSpecState in CMD 48S600Impermissible elec-tronics temperature• Temperature of the electronicsin the non-specified range • Check ambient temperature• Insulate electronics• Use instrument with highertemperature rangeBit 8 ofByte 14 … 24S601Overfilling• Danger of vessel overfilling • Make sure that there is nofurther filling• Check level in the vesselBit 9 ofByte 14 … 24S603Impermissible oper-ating voltage• Operating voltage below speci-fied range • Check electrical connection• If necessary, increase operatingvoltageBit 11 ofByte 14 … 24Tab. 8: Error codes and text messages, information on causes as well as corrective measuresCodeText messageCause Rectification DevSpecState in CMD 48M500Error during the re-set "delivery status"• The data could not be restoredduring the reset to deliverystatus• Repeat reset• Load XML file with sensor datainto the sensorBit 0 ofByte 14 … 24Function checkOut of specificationMaintenance