Through this selection, the sensor is adapted optimally to theapplication or the location and measurement reliability under thevarious basic conditions is increased considerably.Enter the requested parameters via the appropriate keys, save yoursettings with [OK] and jump to the next menu item with the [ESC] andthe [->] key.With this selection, the operating range of the sensor is adapted to thevessel height and the reliability with different frame conditions isincreased considerably.Independent from this, the min. adjustment must be carried out.Enter the requested parameters via the appropriate keys, save yoursettings with [OK] and jump to the next menu item with the [ESC] andthe [->] key.Also the vessel form can influence the measurement apart from themedium and the application. To adapt the sensor to these measure-ment conditions, this menu item offers you different options for vesselbottom and ceiling in case of certain applications.Enter the requested parameters via the appropriate keys, save yoursettings with [OK] and jump to the next menu item with the [ESC] andthe [->] key.Because a radar sensor is a distance measuring instrument, thedistance from the sensor to the product surface is measured. To havethe real product level displayed, an allocation of the measureddistance to the percentage height must be made. To carry out thisadjustment, the distance is entered with full and empty vessel. If thesevalues are not known, an adjustment with the distance values, e.g.10 % and 90 % is also possible. Starting point for these distancespecifications is always the seal surface of the thread or flange. Bymeans of these settings, the real level is calculated.Setup/Vessel height,measuring rangeSetup/Vessel formSetup/Adjustment40 VEGAPULS SR 68 • 4 … 20 mA/HART two-wire6 Set up with the indicating and adjustment module38294-EN-110209