Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 47 -NOTE:When starting up the UPS this PCB has also to be reset when a message for closing the BCB appears.CAUTION:Even at switched off input mains, a dangerous high voltage is still present inside the UPS!The interconnection of the battery symmetry monitoring PCB is shown in a wiring diagram in annex.6.3 Relay PCBThe relay PCB is used to for transferring alarm and status messages to a remote location.Alarm PCBThe currently used definition of the contacts and LED is at hand on a adhesive label adjacent to the PCB.The default setting is as follows:Relay Description Alarm / Status ContactsRL1 Collective fault A30 1 – 2 closedRL2 Mains fault A01 4 – 5 closedRL3 Battery discharged A09 7 – 8 closedRL4 Inverter out of tolerance A13 10 – 11 cosedRL5 Load supplied by bypass A16 13 – 14 closedRL6 Rectifier OK S01 16 – 17 openRL7 Load supplied by inverter S04 19 – 20 openRL8 Bypass OK S06 22 – 23 open6.4 SNMP-AdaptorThe standard UPS can be monitored by using an SNMP-adaptor. It is provided with two serial interfaces. Interface COM1is for communication with the UPS of WÄRTSILÄ JOVYATLAS EUROATLAS. Interface COM2 is for configuration pur-poses, for connection of an additional (special) modem or for MODBUS-applications.CHARACTERISTICS:- 32-Bit RISC-processor, 8MB-RAM, 4MB Flash- supported protocols: SNMP, HTTP, Telnet, UPSMON, PPP/ SLIP, SMTP und FTP- 10/100 Mbit Ethernet-connection- 2 serial RS-232 Interfaces- Integrated WEB-Server- Visualisation by UPSMON, JAVAMON, UNMS, NMS, WEB-Browser or TELNET- Support UPS-MIB RFC1628- To be updated through the network- Fits to all JOVYATLAS UPS-seriesThe connection of a SNMP adaptor is shown in diagram X0012400.VP3 in appendix.iiCN1PB218002APB218004A M11 3 5 7 9 11 13 15 17 19 21 232 4 6 8 10 12 14 16 18 20 22 24DL1 DL2 DL3 DL4 DL5 DL6 DL7 DL8RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8