30BTechnical Condition of Specified Devices • 15Carrier Rail PropertiesWAGO-I/O-SYSTEM 750INTERBUSMechanical strength acc. to IEC 61131-2Test specification Frequency range Limit value5 Hz f < 9 Hz 1.75 mm amplitude (permanent)3.5 mm amplitude (short term)9 Hz f < 150 Hz 0.5 g (permanent)1 g (short term)IEC 60068-2-6 vibrationNote on vibration test:a) Frequency change: max. 1 octave/minuteb) Vibration direction: 3 axes15 gIEC 60068-2-27 shockNote on shock test:a) Type of shock: half sineb) Shock duration: 11 msc) Shock direction: 3x in positive and 3x in negativedirection for each of the three mutually perpendicular axesof the test specimenIEC 60068-2-32 free fall 1 m(module in original packing)*) QP: Quasi PeakNoteIf the technical data of components differ from the values described here, thetechnical data shown in the manuals of the respective components shall bevalid.