WAGO-I/O-SYSTEM 750 XTR Device Description 15750-637/040-001 Inc. Encoder 24 VDC Diff 32Bit XTRManualVersion 1.1.0Use a power supply module!Use a power supply module for field-side power supply of downstream I/Omodules.Mixed operationMixed operation (standard/XTR modules) within a node is possible when groupsof modules are electrically isolated on the field side (i.e., electrically isolatedpower supply).The field voltage and the system voltage are electrically isolated from each other.Use an appropriate supply module!Use an appropriate supply module (e.g., 750-602/040-000) if an electricallyisolated voltage supply is required!Increased interference!For standard-compliant application in substation instrumentation and control,telecontrol systems, railway technology or shipbuilding certified operation,field-side power supply filter 750-624/040-001 or power supply filter750-626/040-000 are generally to be used for XTR module groups.The I/O module can be operated with all fieldbus couplers/controllers of theWAGO-I/O-SYSTEM 750 XTR.Observe the instructions for mixed operation when used in mixed operationbehind standard fieldbus couplers/controllers.