130 Commissioning WAGO I/O SYSTEM 750 XTR750-8202/040-001 PFC200 2ETH RS TELE XTRManualVersion 1.2.0, valid from FW Version 03.01.07(13)7.8.1.8 “Ethernet Configuration” PageThe settings for Ethernet TCP/IP are located on the “Ethernet Configuration”page.7.8.1.8.1 “Switch Configuration” GroupTable 60: WBM “Ethernet Configuration” Page – “Switch Configuration” GroupParameter ExplanationInterfacesEnable or disable the switch.Switched Both interfaces are operated with oneIP address.Separated Each interface is operated with its ownIP address.Port MirrorEnable or disable the mirroring of the data trafficbetween the ports.None Both Ethernet ports operating normally.X1 The entire data traffic between X1 andthe PFC system is mirrored at port X2.X2 The entire data traffic between X2 andthe PFC system is mirrored at port X1.Fast Aging enabledSet here the aging time of unused entries in the listof MAC addresses with a port assignment toexternal network stations.This field is only enabled in “switched” mode. Fastaging is only effective in this mode.Disabled An unused address entry becomesobsolete after 200 seconds.Enabled An unused address entry becomesobsolete after 800 microseconds.Broadcast ProtectionSet here the broadcast limit for protection againstoverloads.Disabled No limitation of broadcast packets.1 % ... 5 %Limitation of incoming broadcastpackets to the selected percentage ofthe total possible data throughput(10/100Mbit).Rate LimitSet here the basic limitation of the incoming datatraffic.Disabled No limitation of the incoming data traffic64 kbps …99 mbpsLimitation of the incoming data traffic tothe entered valueClick [Submit] to apply the change. The change is effective immediately.