WAGO I/O SYSTEM 750 XTR Appendix 351750-8202/040-001 PFC200 2ETH RS TELE XTRManualVersion 1.2.0, valid from FW Version 03.01.07(13)14 Appendix14.1 Process Data ArchitectureThe process image for the I/O modules on the local bus is built up word-by-wordin the controller (with word alignment). The internal mapping method for datagreater than one byte conforms to Intel formats.The following section describes the representation for WAGO I/O SYSTEM 750XTR I/O modules in the process image, as well as the configuration of theprocess values.Equipment damage due to incorrect address!To prevent any damage to the device in the field you must always take theprocess data for all previous byte or bit-oriented I/O modules into account whenaddressing an I/O module at any position in the fieldbus node.No direct access from fieldbus to the process image for I/O modules!Any data that is required from the I/O module process image must be explicitlymapped in the CODESYS program to the data in the fieldbus process image andvice versa! Direct access is not possible!