I/O Modules ï 163Process Data Architecture for MODBUS/TCPWAGO-I/O-SYSTEM 750Linux Fieldbus CouplerVibration Velocity/Bearing Condition Monitoring VIB I/O750-645The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a totalof 12 bytes of user data in both the Input and Output Process Image(8 bytes of module data and 4 bytes of control/status). The following tableillustrates the Input and Output Process Image, which have 8 wordsmapped into each image. Word alignment is applied.Input and Output Process Imagebyte DestinationOffset High Byte Low Byte Remark0 - C0/S0 Not usedControl/Status byte(log. Channel 1,Sensor input 1)1 D1 D0 Data bytes(log. Channel 1, Sensor input 1)2 - C1/S1 Not usedControl/Status byte(log. Channel 2 Sensorinput 2)3 D3 D2 Data bytes(log. Channel 2 Sensor input 2)4 - C2/S2 Not usedControl/Status byte(log. Channel 3 Sensorinput 1)5 D5 D4 Data bytes(log. Channel 3 Sensor input 1)6 - C3/S3 Not usedControl/Status byte(log. Channel 4 Sensorinput 2)7 D7 D6 Data bytes(log. Channel 4 Sensor input 2)