18 • 750-631(750-631/000-001) [Incremental Encoder Interface]Process ImageWAGO-I/O-SYSTEM 750I/O ModulesOverview of Inputs and Outputs:In-/Output Type FunctionSignal A and Signal /A Input, TTL Incremental pulse signals for channel ASignal B and Signal /B Input, TTL Incremental pulse signals for channel BSignal C and Signal /C Input, TTL Track signal for the index channel of the sensorShield Input Shield connection for encoder wiringSensor 0 V Output, Vers. Ground for sensor signals and supplySensor +5 V Output, Vers. 5 V supply for encoder+24 V Input, Vers. 24 V supply voltage for the sensor and dataprocessing0 V Input, Vers. Ground for the 24 V supply voltage, internallyconnected to sensor V0Gate Input, 24 V 24 V input for gate signalLatch Input, 24 V 24 V input for Latch signal2.1.2.8 Process ImageUsing the I/O module 750-631, a 6 byte input and output process image can betransferred to the fieldbus coupler / controller via one logical channel. Thedata sent and received is stored in 2 output bytes (D0, D1) and 4 input bytes(D0, D1, D3, D4). The output bytes D2 ... D4 and the input byte D2 arereserved and without function. One control byte (C0) and one status byte (S0)are used to control the data flow.AttentionThe representation of the process data of some I/O modules or their variationsin the process image depends on the fieldbus coupler/-controller used. Pleasetake this information as well as the particular design of the respectivecontrol/status bytes from the section "Fieldbus Specific Design of the ProcessData" included in the description concerning the process image of thecorresponding coupler/controller.Input data Output dataS0 Status byte C0 Control byteD0 Counter value byte 0 (LSB) D0 Setpoint value byte 0 (LSB)D1 Counter value byte 1 (MSB D1 Setpoint value byte 1 (MSB)D2 reserved D2 reservedD3 Latched value byte 0 (LSB) D3 reservedD4 Latched value byte 1 (MSB) D4 reserved