38 • 750-631/000-010, 750-631/000-011 [Incremental Encoder Interface]Process ImageWAGO-I/O-SYSTEM 750I/O ModulesThe latch and gate inputs are 24V.Overview of Inputs and Outputs:In-/Output Type FunctionSignal A and Signal /A Input Incremental pulse signals for channel ASignal B and Signal /B Input Incremental pulse signals for channel BSignal C and Signal /C Input Track signal for the index channel of the sensorShield Input Shield connection for encoder wiringSensor 0 V (U 0) Output,power supplyGround for sensor signals and supplySensor +5 V (U e ) Output,power supply5 V supply for encoder+24 V Input,power supply24 V supply voltage for the sensor and dataprocessing0 V Input,power supplyGround for the 24 V supply voltage, internallyconnected to sensor U 0Gate Input, 24 V 24 V input for gate signalLatch Input, 24 V 24 V input for Latch signalExt. Error Input, low-sideswitchingInput for alarm output of sensor2.1.4.8 Process ImageUsing the I/O module 750-631/000-010 or 750-631/000-011, a 6 byte inputand output process image can be transferred to the fieldbus coupler / controllervia one logical channel. The data sent and received is stored in 2 output bytes(D0, D1) and 5 input bytes (D0 … D4). The output bytes D2 ... D4 arereserved and without function. One control byte (C0) and one status byte (S0)are used to control the data flow.AttentionThe representation of the process data of some I/O modules or their variationsin the process image depends on the fieldbus coupler/-controller used. Pleasetake this information as well as the particular design of the respectivecontrol/status bytes from the section "Fieldbus Specific Design of the ProcessData" included in the description concerning the process image of thecorresponding coupler/controller.