Document #10-32813 Rev A; June 07, 2019 Page 46 of 69Z1_DEV1_HardwareId 1 0 1 1 1 1 0 DEV 1 Hardware IDZ1_DEV1_DateCode 1 0 1 1 1 8 0 DEV 1 Date CodeZ1_DEV1_ModelNumber 1 0 1 1 1 9 0 DEV 1 Model NumberZ1_DEV1_DeviceName 1 0 1 1 1 11 0 DEV 1 Device NameZ1_DEV1_FirmwareVersion 1 0 1 1 1 17 0 DEV 1 Firmware VersionZ1_DEV1_SerialNumber 1 0 1 1 1 32 0 DEV 1 Serial NumberZ1_VAR1_Type 1 0 1 2 1 1 0 VAR 1 TypeZ1_VAR1_Digital 1 0 1 2 1 2 0 VAR 1 DigitalZ1_VAR1_Analog 1 0 1 2 1 3 0 VAR 1 AnalogZ1_DSP1_DisplayUnits 1 0 1 3 1 5 0 DSP 1 Display UnitsZ1_TST1_Tick 1 0 1 16 1 6 0 TST 1 TickZ1_TST1_EventLog 1 0 1 16 1 8 0 TST 1 Event LogZ1_AST1_Member1 1 0 1 19 1 1 0 AST 1 Member 17. Create a new HTML page “sd:\Https\Zone01.html” using the user-defined tokens above to display informationabout the intermodule bus device at Zone 1. Use the default HTML page “Index.html” as a guide. Open the web pagefrom the Https directory to validate the design (but without live data)..8. Save and close all files on the MICRO SD and NOR FLASH drives. Eject both drives to unmount them from the PC9. Reset the RMA PLUS.10. Now you should be able to open a web browser and navigate to the RMA PLUS using the IP address or host namei.e. http://rma-/Zone01.html or http://192.168.0.100/Zone01.html and see the new HTML page with livedata for Zone 1.Notesl HTML files are stored on the micro SD card by default. This path cannot be changed at run time with a setup file key.l The HTTP server cannot return web pages if the SD drive is mounted to the PC.l Dynamic token replacement only occurs in HTML files (*.html, *.htm).l The current implementation provides for 15 connections. Each file requires a connection. Using the default web pageas an example, there should be a maximum of three connections created by the request for Index.html: 1) indext.html;2) favicon.ico; 3) logo.png. This, of course, varies by browser, caching, timing, etc.l The HTTP Server supports all data typesl You may download or create links to any file on any of the RMA PLUS drives via HTTP. See the event log example onthe default HTML page. Valid drive names are “sd:”, “nor:” and “ram:”l Only read operations are supported via HTTP Server.l Tested with Internet Explorer and ChromeTFTP ServerThe RMA PLUS implements a Trivial File Transfer Protocol (TFTP) server for accessing files on the RMA PLUS in asimilar fashion to USB.This service is enabled by default for all model numbers. It may be disabled by writing “No” on the TFTP Server Enablemember, and then resetting the RMA PLUS.MemberIDMember Name DataTypeAccess NV Min Max Default Comments9 0x09 TFTP Server Enable ENUM16 RW F -- -- 106 59: No 106: YesEthernet 70 (0x46) Instance 2