PG 10 OF 20M0054�07 J ULY 2019Gas-Fired Tandoor CEInstallation and Operation ManualGAS SPECIFICATIONSGAS INLET PRESSUREFor Tandoors running on natural gas, an inlet pressure of 13�6 mbar (5�5" W�C�) is recommended to ensure optimum Tandoorperformance� Incoming gas pressure below this pressure will affect Tandoor performance, the lower the pressure the greater thenegative impact� If the gas supply pressure is greater than 34 mbar (14" W�C� or 1/2 psi), an external regulator, supplied by others,is REQUIRED to lower the gas pressure to the acceptable range� Issues caused by low or high gas pressure are installation issues,and will not be covered under the Warranty�For Tandoors running on LP, the recommended inlet pressure to ensure optimum Tandoor performance is 25 mbar (11" W�C�)Incoming gas pressure below this range will affect Tandoor performance, the lower the pressure the greater the negative impact� Ifthe gas supply pressure is greater than 34 mbar (14" W�C� or 1/2 psi), adjustment to the supplied external regulator is REQUIRED tolower the gas pressure to the acceptable range� Issues caused by low or high gas pressure are installation issues, and will not becovered under the Warranty�For all installations, follow best practices for proper gas line pipe sizing for the line serving the Tandoor� To insure proper operation,all gas piping and fittings leading up to the Tandoor should have an inside diameter equal to or greater than that of the Tandoorgas connection� Also make sure that a readily accessible shut off valve (supplied by others) is installed near the Tandoor, and inaccordance with all applicable codes� Shut off valves must be of the full-flow type, and not introduce any restriction into the gas line�Use a properly sized flexible pipe and quick disconnect device approved for this application� When using a flexible connector makesure that its design does not present any reduction in pipe diameter or other restriction� Tandoor issues caused by improper pipesizing, improper shut off valves, restrictive connectors, or any other deficiency in the gas supply design or installation will not becovered under the Tandoor warranty�THIS APPLIANCE IS NOT FOR USE WITH SOLID FUELGAS CONNECTIONThe gas connection is made at the lower rear of the appliance� Have a licensed gas installer provide the hookup and test allfittings and pipe connections for leaks� Use approved gas leak detectors (soap solutions or equivalent) over and around the fittingsand pipe connections to check for leaks� DO NOT USE FLAME TO TEST FOR LEAKS!This appliance is equipped with casters; it must be installed using the casters supplied with an approved gas connector/quickdisconnect device in accordance with all pertinent national and local regulations� It must also be installed with restraining meansto guard against transmission of strain to the connector�IMPORTANT: The gas supply to this appliance should be equipped with an individual appliance shutoff valve that is capableof completely isolating the appliance from the main gas supply� This valve should be installed in such a manner as to be readilyaccessible to the operator of the appliance�The Wood Stone gas-fired Tandoor is equipped with a 12�7mm (1/2") FBSPT female gas connection, located on the undersideof the rear of the unit� Anchor points for the restraining means are provided on the underside of the Tandoor; these are holespunched in the rear portion of the drip/debris pan rails�Natural Gas (NG): Maximum inlet gas pressure must not exceed 34 mbar (14" W.C. or 1/2 psi)Propane (LP): Maximum inlet gas pressure to the Tandoor, after the external regulator (if used),must not exceed 34 mbar (14" W.C. or 1/2 psi)NG: Minimum inlet gas pressure: 13.6 mbar (below will affect oven performance)LP: Minimum inlet gas pressure: 25 mbar (below will affect oven performance)