ACCESS LEVEL 2 (Authorised User) CONTROLS & MENU OPTIONSAccess level 2 is available to authorised, trained personnel only. At this level, the panel’sSILENCE/RESOUND SOUNDERS, CONTROL PANEL RESET and INVESTIGATE buttons become active andyou are able to:• Scroll through any fire, pre-alarm or fault conditions that are displayed on the panel’s display• View any disablements or zones that are being tested (if applicable)• Enable or disable zones, sounders, outputs, relays and devices (as appropriate)• Print, display and/or reset the panel’s event history• Set the time and date• Change the entry code to access level 2 from its factory default.Details of how to use the panel’s SILENCE/RESOUND SOUNDERS, CONTROL PANEL RESET andINVESTIGATE buttons can be found below.Entering access level 2ON PUSH BUTTON VERSIONS OF THE PANEL:-Entry to access level 2 requires the input of a special four digit code. Press the MENU button on thepanel’s front and when the ENTER ACCESS LEVEL 2? prompt appears, press the accept 4button. Thefollowing message will appear on the display:-Enter the access level 2 code using the 5(1) 4(2) 6(3)3(4) buttons as appropriate. The default codeis 3 3 3 3 (four presses of the6button). If this does not work, the code may have been changed by anauthorised user/engineer. A record of any changes should appear on the System Setup Data Chart onpage 20 of this user manual. If they do not, contact your maintenance company for advice.ON KEYSWITCH VERSIONS OF THE PANEL:-Entry to access level 2 is gained by turning the panel’s keyswitch to the armed position.Silencing the alarm soundersTo silence any active alarm sounders, enter access level 2 (see above) and momentarily press theSILENCE/RESOUND SOUNDERS button. The alarm sounders will cease to sound and the panel’sGeneral Fire and relevant Fire Zone LEDs will go steady.Should a fire condition occur on another zone whilst the alarm sounders are silenced, the panel:-• Will sound the sounders programmed for activation by the new zone(s) in alarm• Will flash its General Fire and appropriate Zone LED(s) for any new zone(s) in alarm• May, if programmed, automatically reactivate the silenced alarm sounders and flashany related Fire Zone LED(s).Resounding the alarm soundersMomentarily pressing the SILENCE/RESOUND SOUNDERS button when the alarm sounders aresilenced will resound them. Pressing the SILENCE/RESOUND SOUNDERS button again will silence thealarm sounders.Resetting the panelAfter the cause of an alarm has been cleared and the alarm sounders have been silenced (see above),the panel can be reset by pressing the CONTROL PANEL RESET button.The panel will give a double beep to indicate the reset process has started and, after a few seconds,the Fire Zone LEDs and General Fire LED will go out to indicate the process is complete. If there arestill any fire conditions on any zones, the panel will go back into alarm as before.Note that the panel’s INVESTIGATE button is only active if an engineer has programmed one ormore zones to operate with a 1st-stage investigation delay period (see page 10 for detailedinformation on this feature).Enter Access Level 2 code:XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANELXFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 14 of 28