XTBA DALI Watch Manual Page 24 of 26Product # - 03/2013© XTBA 1986 – 2013The XTBA QUICK SET UP GUIDE TO DALIIf you have just walked into an installation, you are in a hurry and the client isin the corner sharpening an axe, then the following might be useful to saveyou reading through the delights of the entire manual!Installation installed and connected but not set up or much else?1 - Plug in the mains adaptor first and then connect the XTBA DALI Watch toany point of the DALI cable.2 - Is the blue LED flashing? If no go to 3. If flashing there is no DALI busspower so you need to add one as follows: Press the function key until:L O C A L B U S S P S U O F FY e s t o t o g g l ePress the Yes key to turn on the power and then the function key to get backto the main menu loop.3 – Press the function key until:D I S C O V E R P R O G R A M A L Ly e s t o e n t e r o r m e n u4 – Press the Yes button and the message ‘WILL ERASE ALL DATA’ will bedisplayed. Press Yes again to start discovery.5 – The XTBA DALI Watch will erase all data and discover the first device, atthe end of the search the device to be programmed will be lit to 50% and thedisplay will go to:S . A D D R E S S = 1m e N u = r e j e c t y e s = s e n dUsing the up/down keys set the address you would like the device to be andthen press Yes.6 – Repeat step 5 until COMPLETE (number of devices) FOUND displays.7 – The devices will have had their defaults set in discovery as follows:Power On Level = 1, Minimum Level = 1, System Failure Level = 0, Max Level= 254. Following discovery you can change these settings in Quick Set Up ifneeded.Check it all worked8 – Press the Function button until TRANSMIT DALI and press Menu, pressMenu until ADJUST ONE LEVEL appears then press Yes and the display willchange to:A D D R E S S 1 T O 0 %L / R = A D D U / D = L E V E L