Chapter 3 Deployment Manual VIPA System 200V3-26 HB97E - IM - RE_208-1DPx1 - Rev. 14/05Overall resetStarting with the firmware version V3.0.6 of the DP masters, you have thepossibility to request an overall reset at the DP master.An overall reset clears all data in the Flash-ROM.1. Turn on the power supply of the System 200V.2. Push the operating mode lever of the master module in position MR.Hold it for app. 9s.→ first, the MC-LED blinks 3 times. For 3s the blinking switchesinto permanent on. Then, the IF-LED blinks 3 times andswitches to permanent on.3. Release the lever and tip it within 3s once more in pos. MR.→ The content of the Flash-ROM is deleted. The operation hasbeen executed properly when the green R-LED blinks 3 timesand the IF-LED is permanent on.ClearREIFDEMCREIFDEMCREIFDEMCREIFDEMCREIFDEMCREIFDEMCRNSTMROK3xRNSTMR3s3xRNSTMR TipREIFDEMCREIFDEMC3xRNSTMR 9s max. 3sAs soon as you switch the master to RUN, this boots and starts withits default parameters at the bus.Default parameter: Address: 2, Transfer rate: 1.5MBaudIf there is a valid profibus project in the CPU, this is automaticallytransfered via backplane bus into the RAM of the 1 st master after Power ON- independet from position of operating mode lever.GeneralExecute an overallresetProjectengineering viaCPU after power-on to first master