YASKAWA ELECTRIC TOEP C710606 27C - AC Drive J1000 - Quick Start Guide EN 318 Instructions for UL and cUL8 Instructions for UL and cUL UL Standards ComplianceThis drive is tested in accordance with UL standard UL508C, File No. E131457 andcomplies with UL requirements. To ensure continued compliance when using this drive incombination with other equipment, meet the following conditions: Installation AreaDo not install the drive to an area greater than pollution severity 2 (UL standard). Ambient TemperatureIP20/NEMA Type1 enclosure: -10 to +40CIP20/IP00 Open-Chassis enclosure: -10 to +50CFinless Type: IP20 enclosure: -10 to +50C Main Circuit Terminal WiringYASKAWA recommends using UL-listed copper wires (rated at 75C) and closed-loopconnectors sized for the selected wire gauge to maintain proper clearances when wiring thedrive. Use the correct crimp tool to install connectors per manufacturer recommendation.The following table lists a suitable closed-loop connector manufactured by JST Corporation.Table 1 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)Wire Gaugemm2 (AWG) Terminal Screws Crimp TerminalModel NumberTightening TorqueNm (lbin.)0.75 (18) M3.5 R1.25-3.5 0.8 to 1.0 (7.1 to 8.9)M4 R1.25-4 1.2 to 1.5 (10.6 to 13.3)1.25 (16) M3.5 R1.25-3.5 0.8 to 1.0 (7.1 to 8.9)M4 R1.25-4 1.2 to 1.5 (10.6 to 13.3)2 (14)M3.5 R2-3.5 0.8 to 1.0 (7.1 to 8.9)M4 R2-4 1.2 to 1.5 (10.6 to 13.3)M5 R2-5 2.0 to 2.5 (17.7 to 22.1)M6 R2-6 5.4 to 6.0 (47.8 to 53.1)3.5/5.5 (12/10)M4 R5.5-4 1.2 to 1.5 (10.6 to 13.3)M5 R5.5-5 2.0 to 2.5 (17.7 to 22.1)M6 R5.5-6 5.4 to 6.0 (47.8 to 53.1)M8 R5.5-8 9.9 to 11.0 (87.6 to 97.4)