6 Related Drive Parameters28 YASKAWA ELECTRIC SIEP C730600 91C YASKAWA AC Drive Option SI-EM3 Technical ManualTable 7 Option MonitorsF7-15(03F3)<11> <12>Communication Speed SelectionSets the communication speed.10: 10/10 Mbps100: 100/100 Mbps101: 10/100 Mbps102: 100/10 MbpsDefault: 10Range: 10 to 102F7-16(03F4) Timeout Value Sets the detection time for a communications timeout.Note: Set this parameter to 0.0 to disable the connection timeout function.Default: 0.0 sMin: 0.0 sMax: 30.0 sH5-11(043C)Communications ENTER FunctionSelectionSelects whether an Enter command is necessary to change parametervalues via MEMOBUS/Modbus communications.0: Parameter changes are activated when ENTER command is written1: Parameter changes are activated immediately without use of ENTERcommandDefault: 0 <13>Range: 0, 1<1> Set b1-02 = 3 to start and stop the drive with the Modbus TCP/IP master device using serial communications.Set b1-01 = 3 to control the frequency reference of the drive via the master device.<2> Setting this parameter to 3 or 4 will cause the drive to continue operation after detecting a fault. Take proper measures such as installing anemergency stop switch when using settings 3 or 4.<3> Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are available in A1000 software versions PRG: 1021 andlater.<4> The setting range for 1000-Series drives is different for different software versions. Refer to the instruction manual of a specific drive for moreinformation.<5> Control method availability of this parameter depends on product series. 1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.In AOLV/PM, this value is read as the Torque Limit. GA700, GA800 Drives: Parameter is available in OLV, CLV, AOLV, AOLV/PM, CLV/PM, and EZOLV.In OLV and EZOLV, this value is read as the Torque Limit.<6> The setting specifies that network communications provide the torque reference or torque limit. The motor may not rotate if the PLC does notsupply a torque reference or torque limit.<7> Set F7-01 to F7-12 when F7-13 is set to 0.<8> Not available on 1000-series drives.<9> Cycle power for setting changes to take effect. Set F6-15 to 1 (Enable), to have settings take effect immediately on non-1000 series drives.<10> Set F7-01 to F7-04 when F7-13 is set to 0. All IP Addresses (F7-01 to F7-04) must be unique.<11> Set F7-15 when F7-14 is not set to 1.<12> Only the first portion of the setting is used. The second portion is ignored.<13> The default setting is different for different product series. Refer to the instruction manual of a specific drive for more information.No. Name Description RangeU6-80 to U6-83 OPT IP ADR 1 to 4Displays IP Address currently available;• U6 -80: First octet• U6 -81: Second octet• U6 -82: Third octet• U6 -83: Forth octet0 to 255U6-84 to U6-87 Online Subnet 1 to 4Displays subnet currently available;• U6 -84: First octet• U6 -85: Second octet• U6 -86: Third octet• U6 -87: Forth octet0 to 255U6-88 to U6-91 Online GatewayDisplays gateway currently available;• U6 -88: First octet• U6 -89: Second octet• U6 -90: Third octet• U6 -91: Forth octet0 to 255U6-92 Online Speed Displays CN1 Port 1 link speed currently available. 10: 10 Mbps100: 100 MbpsU6-93 Online Duplex Displays CN1 Port 1 duplex setting currently available. 0: Half, 1: FullU6-97 OPT SPARE 4 Displays option software version. –U6-98 First Fault Displays first option fault. Refer to Option Fault Monitors U6-98and U6-99 on page 43 for details. –U6-99 Current Fault Displays current option fault. Refer to Option Fault Monitors U6-98 and U6-99 on page 43 for details. –No.(Hex.) Name Description Values