4 PROFIBUS-DP Option Components16 YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual{: On / : Flashing / ×: Off◆ Setting Node AddressSet drive parameter F6-30 to a unique node address (Range 0 to 125) on the network.{ × × ×• Checkingconnection withthe drive• Waiting for datafrom the master• PROFIBUS-DP Optionis reading the nodeaddress or parameterconfiguration• Waiting for initial inputdata from master device–× { × ×PROFIBUS-DPOption Self-diagnostics errorThe PROFIBUS-DPOption is damagedCycle power to the drive. If the LEDstatus does not change, replace thePROFIBUS-DP Option× × × Problem connectingto the drive• Problem initializing thedrive and PROFIBUS-DP Option• Incorrect node address• Cycle power to the drive. If the LEDstatus does not change, replace thePROFIBUS-DP Option• Check the node address setting in thedrive (parameter F6-10){ × × {Waiting for datafrom the masterdeviceWaiting for data from themaster device(Set_Parm_Message orChk_Cfg_Message)• Check the network settings in themaster• Make sure the master device isoperating normally• Check the terminal resistance settingson the data line• Look for any problems with the dataline, or if the connector• Check that the data lines are properlyconnected to the drive{ × × Data is incorrect orPROFIBUS-DPOption timed outwaiting for dataThe communicationprocedure in the master isset incorrectly• Check the communication proceduresettings in the master{ × { × Sending or receivingdata – –LED CommunicationStatus Possible Cause SolutionRUN ERR COMM BF