8 CC-Link Data Table30 YASKAWA ELECTRIC TOBP C730600 22B V1000 Option CC-Link Installation ManualNote: If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting theregister. Using RYE (Frequency Reference 2 flag) too often can shorten the performance life ofthe drive's internal memory.RX3 Speed Agree ON: Output frequency is between frequency referenceand the detection width set to L4-02. –RX4 During Stall Prevention – –RX5 During Undervoltage – –RX6 Terminal P1 Function Multi-function output: H2-02 (H2-02 = 0: DuringRun)RX7 Terminal P2 Function Multi-function output: H2-03 (H2-03 = 2: SpeedAgree 1)RX8, 9 Reserved – –RXA CC-Link Option Fault Comm. error between drive and CC-Link device –RXB Monitoring MotorRevolutions ON: Currently monitoring motor revolutions.Data is stored inremote registerRW R1 .RXC Obtain Monitor Data ON: Monitor data has been updated. –RXD Frequency Setting Ready 1 ON: Displays the main frequency reference that has beenset. –RXE Frequency Setting Ready 2ON: Displays the data set to d1-01 (Frequency Reference1).Note: Also sets the main frequency reference at the sametime.–RXF Command Code ExecuteCompleteON: Displayed after the specified command code hasbeen executed.RXF signal switches off when the RYF command is nolonger present.–RX10to 19 Reserved – –RX1A Error ON: Fault occurred on the drive side. –RX1B Remote Station Ready ON: Drive is ready to operate. –RX1Cto 1F Reserved – –Device Signal Name Description Default